Features and Benefits
-
Redundant dual 24
VDC power inputs
-
Relay output warning
for power failure
and port break alarm
-
Broadcast storm
protection
-
Transparent
transmission of VLAN
tagged packets
-
-40 to 75˚C
operating
temperature range (T
models)
Introduction
The EDS-305/308 are
5-port and 8-port
Ethernet switches that
provide an economical
solution for your
industrial Ethernet
connections. The
built-in relay warning
function alerts network
engineers when power
failures or port breaks
occur, and the switches
are designed for harsh
industrial environments,
such as in hazardous
locations (Class I, Div.
2/ATEX). The switches
comply with FCC, TÜV, UL,
and CE standards, and
come in two model types.
Standard operating
temperature range models
(0 to 60°C) and wide
operating temperature
range models (-40 to
75°C). Both models
undergo a 100% burn-in
test to ensure that they
fulfill the special
needs of industrial
automation control
applications. The
EDS-305/308 switches can
be installed easily on a
DIN-Rail or in a
distribution box.
|
|
|
• Technology: |
|
Standards |
IEEE 802.3 for 10BaseT
IEEE 802.3u for 100BaseT(X)
and 100Base FX
IEEE 802.3x for Flow Control |
|
Processing Type |
Store and Forward |
|
Flow Control |
IEEE802.3x full duplex, back
pressure flow control |
|
• Interface: |
|
RJ45 Ports |
10/100BaseT(X) auto
negotiation speed, Full/Half
duplex mode, and auto MDI/MDI-X
connection |
|
Fiber Port(s) |
100BaseFX ports (SC/ST
connector) |
|
LED Indicators |
PWR1, PWR2, Fault, 10/100M (TP
port), 100M (Fiber port) |
|
DIP Switches |
Port break alarm mask |
|
Alarm Contact |
1 relay output with current
carrying capacity of 1A @ 24
VDC |
|
• Optical Fiber |
 |
|
• Physical Characteristics: |
|
Housing |
Metal, IP30 protection |
|
Weight |
630 g |
|
Dimensions |
53.6 x 135 x 105 mm (2.11 x
5.31 x 4.13 in) |
|
Installation |
DIN-Rail mounting, wall
mounting (with optional kit) |
|
• Environmental Limits: |
|
Operating Temperature |
Standard Models: 0 to 60°C
(32 to 140°F)
Wide Temp. Models: -40 to
75°C (-40 to 167°F) |
|
Storage Temperature |
-40 to 85°C (-40 to 185°F) |
|
Ambient Relative Humidity |
5 to 95% (non-condensing) |
|
• Power Requirements: |
|
Input Voltage |
24 VDC (12 to 48 VDC),
redundant inputs |
|
Input Current |
EDS-305: 0.13 A @ 24 V
EDS-305-M/S: 0.17 A @ 24 V
EDS-308: 0.13 A @ 24 V
EDS-308-M/S: 0.21 A @ 24 V
EDS-308-MM/SS: 0.26 A @ 24 V |
|
Overload Current
Protection |
EDS-305, EDS-305-M,
EDS-305-S, EDS-308: 1.1 A
EDS-308-M/S/MM/SS: 1.6 A |
|
Connection |
1 removable 6-pin terminal
blocks |
|
Reverse Polarity
Protection |
Present |
|
• Agency Approvals: |
|
EMI |
FCC Part 15, CISPR (EN55022)
class A |
|
EMS |
EN61000-4-2 (ESD), level 3
EN61000-4-3 (RS), level 3
EN61000-4-4 (EFT), level 3
EN61000-4-5 (Surge), level 3
EN61000-4-6 (CS), level 2 |
|
Safety |
UL508, UL60950-1, CSA C22.2
No. 60950-1, EN60950-1 |
|
Hazardous Location |
UL/cUL Class I, Division 2,
Groups A, B, C and D; ATEX
Zone 2, Ex nC IIC |
|
Shock |
IEC60068-2-27 |
|
Freefall |
IEC60068-2-32 |
|
Vibration |
IEC60068-2-6 |
|
MTBF (meantime between
failures) |
Time:
EDS-305 series: 422,000 hrs
EDS-308 series: 255,000 hrs
Database: MIL-HDBK-217F, GB
25˚C |
|
Maritime |
DNV, GL |
|
|
|
|